PROCESS RADIO CONTROL Two way communication four channels
of Bi-Directional, Full Duplex 12-bit analog INPUTS and OUTPUTS allowing
for complete control and monitoring
The four input voltage signals from the Master and Slave are transmitted
to each other and are converted to respective outputs. Therefore the
four input voltage signals from the Master are transmitted to the Slave.
The Slave converts them into a proportional output signal. The same
occurs when the Slave sends its input voltage signals to the Master
|
|
Universal Output |
| Supply power |
24 VAC/DC ±10% @ 500 mA |
| Outputs (4) |
Selectable digital or analog |
| Digital |
10-48 VDC
open collector |
| Analog |
0-20 mA, 0-10 VDC |
| Sensor |
4-20 mA, 2-10 VDC |
| Impedance |
<650ohm mA, >10ohm V |
| D/A resolution |
12-bit converter |
| LBI option |
SPST low battery indicator |
| Ambient temp |
14° to 140° F (-10° to 60°
C) |
| Ambient RH |
5% to 95% RH noncondensing |
| Connection |
Terminal screws |
| Housing |
NEMA 4, plenum rated |
| Weight |
5.2 lb (2.40kg)
each unit |
| Dimensions |
12"W x 14"H x
6"D (30 x 35 x 15 cm) |
|
|
Radio |
| Frequency |
923.58 MHz |
| Receiver |
sensitivity -110 dBm |
| Modulation |
Direct sequence, spread spectrum |
| Data rate |
19.2 KBPS |
| Antenna |
Included 9 dBi Yagi antenna |
| Approvals |
FCC CFR part 15.247 |
|
Address Structure |
| Facility address
code |
Unique for each system |
| Transmitter power |
50 mW |
| Setup |
Software
selectable |
| Four channel |
bi directional
|
|
4Ch analog/digital 2
Channel Digital
|
|