Current Status Switch

|
SPECIFICATIONS
| |
Switch |
rating 1-135 VAC/DC, 0.3A |
| |
Switch type |
Normally open, solid state |
| |
Off-state |
leakage Zero |
| |
Polarity |
Not polarity sensitive, switch AC or
DC |
| |
CS1A |
1A 1-250A* |
| |
|
* For loads with higher
FLA.s and for
larger diameter conductors, use an external current transformer. |
| |
|
Max currents |
| |
Continuous |
250A |
| |
For 6 sec |
500A |
| |
For 1 sec |
1000A |
| |
Monitored |
frequency 60 Hz max, 6 Hz min** |
| |
|
** Specifically designed to
accommodate variable-speed drives. Monitored frequency may go to
less than 6 Hz without contact chattering. |
| |
Operating |
temp -58°F to 149°F (-50°C to 65°C) |
| |
Case |
ABS (meets UL flammability rating
94V-0) |
| |
Insulation |
600V |
| |
Weight |
0.25 lb (0.11 kg) |
| |
Approvals |
UL and ULC listed, File #E170092; CE
Certified |
|
Dimensions:
 |
Solid-state switches that operate when the AC
current level sensed by the internal current transformer exceeds a fixed set
point. Internal circuits are totally powered by induction from the conductor
being monitored. There is zero off-state leakage current in the solid-state
relay output that can switch AC or DC circuits. Currents up to 250A can be
monitored. For higher currents or larger diameter conductors, an external
current transformer should be used.
|